Plan Review Notes For Permit 26040830
Permit Number 26040830
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2026-04-29 15:34:37.00000SHEET PV3: IS A 50A BACKFED BREAKER INTENDED IN THE
 MAIN SERVICE PANEL? (PCS LIMIT = 30A).
 SHEET PV4: THE AC CURRENT LABEL MUST SHOW THE ACTUAL PV
 SYSTEM MAXIMUM CURRENT OUTPUT (PER INSTALLED
 INVERTERS). THE VALUE SHOWN DOES NOT CORRESPOND TO ANY
 SYSTEM PARAMETER.
  