-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 26040652
Permit Number 26040652
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2026-04-22 16:09:04.00000SHEET PV-3: INSERT PCS INFORMATION IF FUNCTION IS
 INTENDED TO BE USED; OTHERWISE INCREASE CONDUCTOR SIZE
 AND OVERCURRENT PROTECTION RATING ON UTILITY SIDE OF
 ENPHASE CONTROLLER.
 SHEET PV-4: IF PCS FUNCTION IS USED, PROVIDE LABEL
 INDICATING THIS FUNCTION AND MAXIMUM PROGRAMMED CURRENT
2026-04-22 12:16:25.00000PERMITTING@MYEQUITYSOLAR.COM
 PP INSPECTONS ONLY, MY AMELIA INC