2026-04-21 16:07:53.00000SHEET PV-1: CHANGE SCOPE OF WORK NOTE TO SHOW
 SUPPLY-SIDE TAP
 SHEET PV-3: CHANGE OCPD RATING IN TABLE TO MATCH THAT
 SHOWN ON THE ONE-LINE DIAGRAM, CONDUCTORS IDENTIFIED AS
 #8 & #10. OCPD = 60A, NOT 50A.