-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 26040228
Permit Number 26040228
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2026-04-10 17:05:11.000001] SHEET PV-3:
 A. CHANGE CONDUCTOR ID #8 TO MINIMUM #6 CU
 B. CHANGE NOTE #11 TO SHOW A LINE SIDE TAP (AS
 INDICATED BY ONE-LINE DRAWING)
 C. REMOVE CALLOUTS FOR NOTES 16 & 17 (NOT APPLICABLE)
  
 2] PROVIDE SPECIFICATION DOCUMENTS FOR ENERGY STORAGE
 COMPONENT.
2026-04-10 08:58:57.00000PERMITTING@MYEQUITYSOLAR.COM