Plan Review Notes
Plan Review Notes For Permit 26040157
Permit Number 26040157
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2026-04-10 08:53:33.00000NOC IN ONBASE OR BK 3184 PG 869
2026-04-07 14:14:47.00000SHEET 006:
 1] CHANGE NEW PV DISCONNECT OVERCURRENT PROTECTION TO
 35A MAX OR CHANGE CONDUCTOR ID #3 TO MINIMUM #8CU THWN
 2] SHOW GATEWAY AS EXISTING PER SITE DIAGRAM ON SHEET
 003 (CURRENTLY THE GATEWAY AND THE 60A BREAKER WITHIN
 THE GATEWAY ARE LABELED "N")
  
 SHEET 007: SHOW NEW AC CURRENT/VOLTAGE LABEL AT
 15.8A/240V, TO BE AFFIXED TO NEW PV DISCONNECT.