Date Text
2026-04-02 15:38:04.00000SHEET 006: CHANGE SUPPLY-SIDE TAP CONDUCTORS (ID #4) TO
 MINIMUM #6 CU PER 705.11 (B)
 SHEET 007: SHOW AC CURRENT/VOLTAGE LABEL PER 690.54.
 LABEL #'S 6, 8, & 9 MAY BE REMOVED AS THEY ARE NOT
 APPLICABLE TO THIS INSTALLATION.
2026-04-02 12:33:31.00000NOC IS IN ONBASE OR BK 3183 PG 1105
2026-04-02 09:52:44.00000ROGER.G@BETTEREARTH.SOLAR