2026-03-18 15:57:42.00000SHEET PV3:
 1] CHANGE AC CURRENT VOLTAGE LABEL TO REFLECT 57 AMPS.
 SINCE THE PROPOSED SYSTEM IS COMBINED WITH AN EXISTING
 SYSTEM, THIS LABEL SHOULD BE AFFIXED TO THE PV
 DISCONNECT AND SHOULD SHOW TOTAL SYSTEM OUTPUT. IT IS
 ACCEPTABLE TO INSTALL A LABEL SHOWING 24 AMPS ON THE
 PROPOSED 5700 WATT INVERTER ONLY.
 2] CHANGE CONDUCTOR CALLOUT #4 TO MINIMUM #4 COPPER.
 THE COMBINED SYSTEM CURRENT OUTPUT X 1.25 EXCEEDS 70
 AMPS; #6 COPPER NOT APPROVED.
  
  