2026-04-13 16:11:01.00000PLAN REVIEW #: 26020652
 PROJECT: HILLGROVE HEIGHTS CLUBHOUSE
 LOCATION: 4755 YOUTH CARE LANE
 OCCUPANCY: BUSINESS
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 4/13/26
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED – DOES NOT MEET COUNTY ORDINANCE CHAPTER 12
 ARTICLE 8 SECTION 12.08.120 SUBSECTION B – 1
 SECTION 12.08.120. REQUIRED RECREATION/DISASTER SHELTER
 BUILDING.
 A. APPLICABILITY. M-2, CG-1, CG-2, CG-3, AND RV PARK
 (FUD) ZONING DISTRICTS, AND WITHIN ALL MANUFACTURED
 HOME PARKS, MANUFACTURED HOME SUBDIVISIONS, MOBILE HOME
 PARKS, RV PARKS, CAMPGROUNDS, AND SEASONAL PARKS
 CONTAINING 25 OR MORE LOTS, RENTAL SPACES OR CAMPSITES
 ON WHICH RVS, PARK MODELS, MOBILE HOMES OR MANUFACTURED
 HOMES ARE PLACED AFTER NOVEMBER 14, 1994, IN A MANNER
 REQUIRING A BUILDING PERMIT OR WHICH ARE DEVELOPED
 AFTER NOVEMBER 14, 1994, A RECREATION/DISASTER SHELTER
 BUILDING MEETING THE REQUIREMENTS OF SUBSECTIONS B. AND
 C. BELOW OF THIS SECTION SHALL BE PROVIDED.
 B. ADDITIONAL STANDARDS FOR APPROVAL. A REQUIRED
 RECREATION/DISASTER SHELTER BUILDING SHALL HAVE:
 1. A MINIMUM FLOOR AREA OF AT LEAST 35 SQUARE FEET
 (EXCLUDING KITCHENS, CLOSETS, TOILETS, BATHROOMS,
 PORCHES, BREEZEWAYS AND TERRACES) PER LOT, RENTAL SPACE
 OR CAMPSITE. RV PARKS AND CAMPGROUNDS WHICH DO NOT
 CONTAIN MOBILE OR MANUFACTURED HOMES MAY CALCULATE THE
 MINIMUM REQUIRED AREA BASED ON 50 PERCENT OF THE TOTAL
 NUMBER OF RENTAL SPACES WITHIN THE PARK OR CAMPGROUND;
 AND
 2. A MINIMUM FLOOR ELEVATION AT LEAST TWO FEET ABOVE
 THE ESTABLISHED 100-YEAR FLOOD LEVEL; AND
 3. THE DISASTER SHELTER MUST CONTAIN A KITCHEN; AND
 4. ADEQUATE EMERGENCY LIGHTING AND WATER SUPPLY AND
 ADEQUATE EMERGENCY GENERATORS TO POWER THE ENTIRE
 DISASTER SHELTER FOR A MINIMUM OF 72 CONSECUTIVE HOURS,
 OR UNTIL POWER IS RESTORED, WHICHEVER COMES FIRST; AND
 5. DESIGNED AND CONSTRUCTED TO NO LESS THAN RISK
 CATEGORY IV CONSTRUCTION STANDARDS IN COMPLIANCE WITH
 THE FLORIDA BUILDING CODE, CURRENT EDITION.
 CONSTRUCTION PLANS SIGNED AND SEALED BY A REGISTERED
 ENGINEER AND/OR ARCHITECT, CERTIFYING THAT THE
 STRUCTURE MEETS THE REQUIREMENTS OF THIS PARAGRAPH,
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL AND
 APPROVED BEFORE FINAL DEVELOPMENT ORDERS ARE ISSUED FOR
 NEW MANUFACTURED HOME PARKS, MANUFACTURED HOME
 SUBDIVISIONS, MOBILE HOME PARKS, MOBILE HOMEVVV
 SUBDIVISIONS, RV PARKS, CAMPGROUNDS, AND SEASONAL PARKS
 DEVELOPED AFTER NOVEMBER 14, 1994, CONTAINING 25 OR
 MORE LOTS, RENTAL SPACES OR CAMPSITES AND BEFORE
 ISSUING MORE THAN 25 BUILDING PERMITS FOR PLACEMENT OF
 RVS, PARK MODELS, MANUFACTURED HOMES OR COMBINATION
 THEREOF, IN ANY EXISTING RV PARK, CAMPGROUND OR MOBILE
 HOME PARK AFTER NOVEMBER 14, 1994.
 C. ADDITIONAL REQUIREMENTS.
 1. AN AREA TO SHELTER CRATED HOUSEHOLD PETS OF THE
 RESIDENTS OF THE PARK OR SUBDIVISION SHALL BE PROVIDED.
 SAID AREA MAY BE LOCATED WITHIN THE DISASTER SHELTER,
 OR WITHIN A SEPARATE STRUCTURE. SAID SEPARATE STRUCTURE
 SHALL MEET RISK CATEGORY II, OR HIGHER, CONSTRUCTION
 STANDARDS IN COMPLIANCE WITH THE FLORIDA BUILDING CODE,
 CURRENT EDITION; ALL EXTERIOR GLASS SURFACES MUST BE
 MADE OF IMPACT RESISTANT GLASS OR HAVE STORM SHUTTERS
 IN PLACE; AND THE STRUCTURE SHALL HAVE A GENERATOR
 SUFFICIENT TO POWER AN AIR CONDITIONING UNIT OR FANS TO
 ADEQUATELY COOL THE AREA, FOR A MINIMUM OF 72
 CONSECUTIVE HOURS, OR UNTIL POWER IS RESTORED,
 WHICHEVER COMES FIRST. PET CRATES SHALL SECURELY
 CONTAIN THE ANIMAL AND BE LEAK PROOF. THIS REQUIREMENT
 SHALL BE SATISFIED SHOULD THE PARK OR SUBDIVISION
 PROVIDE THE COUNTY WITH A COPY OF RECORDED COVENANTS OR
 RESTRICTIONS PROHIBITING RESIDENTS FROM HAVING
 HOUSEHOLD PETS AS DEFINED BY THIS CHAPTER.
 2. A PLAN SHALL BE PROVIDED TO THE COUNTY ENGINEER
 SHOWING THE LOCATION OF THE RECREATION/DISASTER SHELTER
 BUILDING ON THE SITE IN RELATION TO THE EXISTING LOTS,
 RENTAL SPACES OR CAMPSITES.
 3. DOCUMENTATION THAT THE GENERATORS REQUIRED PURSUANT
 TO 12.08.120.B., ARE SUFFICIENT.
 REVIEW FEE – $400 AND INSPECTION FEE - $70 = $470