Plan Review Notes
Plan Review Notes For Permit 26020615
Permit Number 26020615
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2026-03-19 11:23:42.00000APPROVED WITH CONDITIONS:HYDRANT IS REQUIREMENTS LISTED
 BELOW
 ON PAGE A2.2
 THE NEAREST EXISTING FIRE HYDRANT TO THE DEVELOPMENT
 PROJECT IS LOCATED NORTH NORTHWEST OF THE NORTHWESTERN
 CORNER OF THE PROPERTY ACROSS US HIGHWAY 27 AT THE
 INTERSECTION OF HEARTLAND BOULEVARD, APPROXIMATELY +/-
 535.0 FEET FROM THE NORTHWEST CORNER OF THE NEW CAR
 WASH BUILDING.
 NFPA 1:18.5.1.5
 WHERE FIRE APPARATUS ACCESS ROADS ARE PROVIDED WITH
 MEDIAN DIVIDERS INCAPABLE OF BEING CROSSED BY FIRE
 APPARATUS, OR WHERE FIRE APPARATUS ACCESS ROADS HAVE
 TRAFFIC COUNTS OF MORE THAN 30,000 VEHICLES PER DAY,
 HYDRANTS SHALL BE PLACED ON BOTH SIDES OF THE FIRE
 APPARATUS ACCESS ROAD ON AN ALTERNATING BASIS, AND THE
 DISTANCES SPECIFIED BY SECTION 18.5 SHALL BE MEASURED
 INDEPENDENTLY OF THE HYDRANTS ON THE OPPOSITE SIDE OF
 THE FIRE APPARATUS ACCESS ROAD.
 NFPA 1:18.5.3 BUILDINGS OTHER THAN DETACHED ONE- AND
 TWO-FAMILY DWELLINGS.
 FIRE HYDRANTS SHALL BE PROVIDED FOR BUILDINGS OTHER
 THAN DETACHED ONE- AND TWO-FAMILY DWELLINGS IN
 ACCORDANCE WITH BOTH OF THE FOLLOWING:
 (1) THE MAXIMUM DISTANCE TO A FIRE HYDRANT FROM THE
 CLOSEST POINT ON THE BUILDING SHALL NOT EXCEED 400 FT
 (122 M).
2026-02-24 15:35:30.00000EMAILED TO J.RAPER + UPLOADED TO FTP SITE.