Date Text
2026-03-16 16:10:33.00000SHEET E-2: PREVIOUS DEFICIENCIES CORRECTED. CONDUCTORS
 USED FOR SUPPLY-SIDE TAP MUST BE MINIMUM #6 COPPER OR
 #4 ALUMINUM, 705.11 (B).