2026-03-13 16:33:40.00000SHEET E-2:
 1] WRITTEN NOTE ON PLANS STATES "TAP AT LINE SIDE".
 ONE-LINE DIAGRAM SHOWS FEEDER TAP (ON LOAD SIDE OF MAIN
 BREAKER). CLEARLY INDICATE INTERCONNECTION POINT. IF
 LOAD SIDE TAP, REMOVE NEUTRAL-TO-GROUND BOND LINK IN PV
 DISCONNECT. SEE 250.24.
 2] THE CORRECT SYSTEM CURRENT OUTPUT IS 34.76 AMPS
 (BASED ON 22 384W MICROINVERTERS). SHOW THIS VALUE ON
 THE LABELS, AS REQUIRED BY 690.54. THE 25% DEMAND
 FACTOR GOVERNS THE SIZE OF CONDUCTORS, EQUIPMENT, AND
 OVERCURRENT PROTECTION; IT SHOULD NOT BE INCLUDED IN
 THE ACTUAL CURRENT OUTPUT LABEL. SEE 690.8 (B)(2) &
 690.9 (B).
 3] SHOW THE RAPID SHUTDOWN GRAPHIC LABEL DEPICTED IN
 FIGURE 690.56 (C).
 REFERENCES ARE FROM THE 2020 NEC.