Plan Review Notes For Permit 26020013
Permit Number 26020013
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2026-03-10 15:42:53.00000SHEET SP-1: ITEMS C AND E IN THE CHART ARE REVERSED,
 LOWER LEFT CORNER OF SHEET.
 SHEET E-2:
 1] IN EXISTING MAIN SERVICE PANEL, THE ILLUSTRATED 150A
 BREAKER DOES NOT AGREE WITH THE DESCRIPTION OF A 200A
 MAIN BREAKER BELOW. SPECIFY EXACT EXISTING OR PROPOSED
 MAIN BREAKER.
 2] IN THE PV DISCONNECT, REMOVE THE NEUTRAL-TO-GROUND
 BOND LINK SHOWN. NEUTRAL CANNOT BE RE-GROUNDED BEYOND
 THE SERVICE DISCONNECT IF USING A LOAD-SIDE (FEEDER)
 TAP.
 3] IN THE SAFETY LABELING SECTION (BOTTOM OF SHEET),
 SHOW ACTUAL SYSTEM VALUES ON THE AC CURRENT/VOLTAGE
 LABEL. SHOW CORRECT SYSTEM AC CURRENT OUTPUT ON THE
 "DUAL POWER SOURCES" LABEL TO BE AFFIXED TO THE METER.
  