-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 25120576
Permit Number 25120576
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2026-01-13 16:51:15.00000CONDITIONAL APPROVAL PER EXAMINER COMMENTS:
 SHEET PV2.0 REQUIRING FIRE PATHS PER FBC-R324.6
 SHEET PV4.0 REGARDING SEPARATION OF GROUNDING AND
 NEUTRAL CONDUCTORS IN PV DISCONNECT (FEEDER-TAP
 INTERCONNECTION) PER NEC 250.24
 TO BE VERIFIED AT INSPECTION.
2025-12-18 08:25:20.00000RUBEN@VOPSSOLUTIONS.COM
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved