Plan Review Notes
Plan Review Notes For Permit 25110693
Permit Number 25110693
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-11-25 15:16:21.00000SHEET PV3:
 1] SHOW CONDUCTOR SIZE (INCLUDING THE PRESENCE OF AN
 EQUIPMENT GROUNDING CONDUCTOR) FOR THE EXISTING FEEDER
 SUPPLYING THE EXISTING 125A LOAD CENTER
 2] CONDUCTOR CALLOUT #4 INDICATES A #10 AWG TERMINATED
 TO A 40A BREAKER (CB5). THIS INFORMATION DOES NOT
 CORRESPOND TO THAT SHOWN IN THE CONDUCTOR TABLE;
 APPEARS TO BE INCORRECT CALLOUT NUMBER, CORRECT AS
 NECESSARY.
 3] SHOW THE INSTALLATION OF A SPD PER 230.67,
 ALTERATION OF SERVICE EQUIPMENT.