-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 25110215
Permit Number 25110215
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-11-12 11:37:05.00000NOC: OR BK 3155 PG 1686
2025-11-10 12:03:15.00000SHEET E-03: SHOW PROPERLY IDENTIFIED DC MAXIMUM SYSTEM
 VOLTAGE LABEL PER 690.53. THE LABEL CURRENTLY INCLUDED
 ON THIS SHEET INDICATES AC VALUES AND IS NOT NECESSARY
 SINCE AN AC CURRENT/VOLTAGE LABEL IS ALSO SHOWN.
 CALCULATE MAXIMUM DC VOLTAGE PER 690.7 AND SHOW THIS
 VALUE ON A LABEL CLEARLY DENOTING THE VALUE AS DC
 VOLTAGE.
 REQUIRED FOR ALL STRING INVERTER SYSTEMS; REFER TO
 EMAIL SENT 11/04/25 FOR MORE INFORMATION.
2025-11-10 08:31:10.00000PERMITS@SUNVENA.COM