Date Text
2025-10-31 16:36:30.00000PLANSHEETS E2 & E3: #4 CU AWG GENERATOR FEEDERS ARE
 UNDERSIZED FOR PROPOSED 150A GENERATOR
 BREAKER/GENERATOR RATING. SHOW CORRECT CONDUCTOR SIZES,
 INCLUDING EQUIPMENT GROUNDING CONDUCTOR, TO REFLECT
 CORRECT VALUES PER TABLE 310.16 AND TABLE 250.122.