-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 25100992
Permit Number 25100992
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2026-02-09 10:34:13.00000REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 2/5/26
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED WITH NOTES
 PAGE AD1.010.0 – SHOWS TEMP CONSTRUCTION FENCE. PLEASE
 MAKE SURE THE FDC AND HYDRANT ARE NOT ENCLOSED INSIDE
 THE FENCED AREA
 CONTACT THE FIRE MARSHAL’S OFFICE FOR ALL LANE
 CLOSURES, FIREWALL INSPECTIONS (SCREW PATTERNS, DRYWALL
 LAYERS, AND FIRE CAULK), ABOVE CEILING INSPECTIONS,
 SPRINKLER INSPECTIONS, FIRE ALARM INSPECTIONS, AND
 FINALS.
 PROVIDE FIRE SPRINKLER PLANS AND FIRE ALARM PLANS.
 ALL FIRE PROTECTION SYSTEMS SHALL BE MAINTAINED DURING
 DEMO AND CONSTRUCTION. IF ANY FIRE PROTECTION SYSTEMS
 ARE DOWN SHALL CONTACT THE FIRE MARSHAL’S OFFICE AND
 PROVIDE A FIRE WATCH.
  
 FIRE WATCH PROCEDURE
 UPDATED 06/30/2022
 YOU ARE REQUIRED TO POST A FIRE WATCH FOR THE FOLLOWING
 REASON(S):
  A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4 HOURS IN A 24-HOUR PERIOD.
  THERE HAS BEEN A FAILURE OF A FIRE PROTECTION
 SYSTEM.
  THERE HAVE BEEN AN EXCESSIVE NUMBER OF
 ACCIDENTAL ACTIVATIONS OR NUISANCE ALARMS. A NUISANCE
 ALARM IS DEFINED AS "ANY ALARM CAUSED BY MECHANICAL
 FAILURE, MALFUNCTION, IMPROPER INSTALLATION, OR LACK OF
 PROPER MAINTENANCE, OR ANY ALARM ACTIVATED BY A CAUSE
 THAT CANNOT BE DETERMINED." (NFPA 72-3.3.5.1)
  A FIRE PROTECTION SYSTEM IS IN A TROUBLE OR A
 SUPERVISORY MODE FOR MORE THAN FOUR HOURS.
 THIS FIRE WATCH IS REQUIRED:
  FOR 24 HOURS A DAY 7 DAYS A WEEK.
  ONLY WHILE THE BUILDING IS OCCUPIED UNLESS THE
 LOCATION IS HIGH HAZARD.
 OWNER’S RESPONSIBILITIES:
 • ENSURE THAT QUALIFIED PERSONNEL ARE PROVIDING THE
 FIRE WATCH.
 • NOTIFY THE MONITORING COMPANY THAT THE FACILITY IS
 UNDER A FIRE WATCH.
 • CONTRACT WITH A CERTIFIED FIRE PROTECTION COMPANY TO
 FIX THE FIRE PROTECTION SYSTEM(S) THAT ARE IMPAIRED.
 • NOTIFY THE FIRE PREVENTION BUREAU AT 863.402.7600 AS
 SOON AS THE SYSTEM IS CERTIFIED OPERATIONAL.
 QUALIFICATIONS OF FIRE WATCH PERSONNEL:
 • MUST BE DEDICATED EXCLUSIVELY AS A FIRE WATCH.
 • FULLY UNDERSTAND THE IMPACT OF THE FIRE PROTECTION
 SYSTEM IMPAIRMENT.
 • KNOW ALL EGRESS ROUTES THROUGHOUT THE BUILDING.
 • HAVE THE ABILITY TO COMMUNICATE ORALLY.
 • HAVE THE ABILITY TO KEEP WRITTEN RECORDS.
 • HAVE THE ABILITY TO WALK THE FACILITY, IDENTIFY
 DANGEROUS SITUATIONS, REPORT AN EMERGENCY, AND ASSIST
 IN AN EVACUATION.
 DUTIES OF FIRE WATCH PERSONNEL:
 • PATROL THE ENTIRE FACILITY EVERY 15 MINUTES.
 • IDENTIFY ANY FIRE OR LIFE SAFETY HAZARDS AND REPORT
 THEM BY:
  CONTACTING 9-1-1 AND REPORTING THE TYPE OF
 EMERGENCY AND EXACT LOCATION.
  IF THE BUILDING IS OCCUPIED, NOTIFY ALL
 OCCUPANTS TO EVACUATE.
  IF THE FIRE ALARM OR PUBLIC ADDRESS SYSTEMS
 ARE OPERATIONAL, USE THEM TO ASSIST WITH THE EVACUATION
 OF THE BUILDING.
  HAVE READY ACCESS TO FIRE EXTINGUISHERS (NOTE:
 FIRE WATCH PERSONNEL WILL NOT PERFORM ANY FIREFIGHTING
 DUTIES BEYOND THE SCOPE OF THE ORDINARY CITIZEN).
 • MAINTAIN A LOG OF FIRE WATCH ACTIVITIES.
 • HAVE A GOOD WORKING KNOWLEDGE OF THE FIRE PROTECTION
 EQUIPMENT AVAILABLE AND BE TRAINED IN HOW TO USE THEM,
 INCLUDING PORTABLE FIRE EXTINGUISHERS.
 REQUIRED LOG ENTRIES OF FIRE WATCH PERSONNEL:
 • ADDRESS OF THE FACILITY
 • NAME OF THE PERSON CONDUCTING THE FIRE WATCH.
 • TIME THEIR SHIFT BEGAN.
 • TIME THEIR SHIFT ENDED.
 • TIMES EACH ROVING PATROL WAS COMPLETED IN THE
 FACILITY.
 • RECORD OF COMMUNICATION(S) TO THE FIRE DEPARTMENT AND
 MONITORING COMPANY.
 • RECORD OF OTHER INFORMATION AS DIRECTED BY THE OWNER
 OR FIRE DEPARTMENT PERSONNEL.
 CANCELLATION PROCEDURES: AFTER ALL REPAIRS ARE COMPLETE
 THE OWNER MUST CALL THE FIRE PREVENTION BUREAU AND
 REQUEST TO HAVE THE FIRE WATCH CANCELLED.
 THE FLORIDA FIRE PREVENTION CODE DEFINES A FIRE WATCH
 AS THE ASSIGNMENT OF A PERSON OR PERSONS TO AN AREA FOR
 THE EXPRESS PURPOSE OF NOTIFYING THE FIRE DEPARTMENT,
 THE BUILDING OCCUPANTS, OR BOTH OF AN EMERGENCY;
 PREVENTING A FIRE FROM OCCURRING; EXTINGUISHING SMALL
 FIRES; OR PROTECTING THE PUBLIC FROM FIRE OR LIFE
 SAFETY DANGERS.
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT THE FIRE
 PREVENTION BUREAU AT (863) 402-7600.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved