-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 25100902
Permit Number 25100902
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-11-05 09:33:02.00000FULL PAYMENT RECEIVED REFERENCE NUMBER: 16887942
2025-10-30 15:36:32.00000SHEET E-01: SHOW A DISCONNECTING MEANS BETWEEN THE
 INVERTER/ESS AND THE GATEWAY, OR AN EQUALLY EFFECTIVE
 MEANS OF SHUTTING DOWN ALL EXPORT POWER FROM THE
 INVERTER/ESS TO DE-ENERGIZE THE INTERIOR BRANCH CIRCUIT
 LOADCENTER IN THE EVENT OF A UTILITY OUTAGE. PER 706.15
 (A) AND HIGHLANDS COUNTY FIRE DEPARTMENT, THIS
 DISCONNECTING MEANS MUST BE ON THE EXTERIOR OF THE
 HOUSE, EXTERNALLY OPERABLE, READILY ACCESSIBLE, AND
 EFFECTIVELY LABELED AS TO ITS PURPOSE.
2025-10-28 08:16:22.00000PERMITS@SUNVENA.COM
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved