Plan Review Notes For Permit 25100899
Permit Number 25100899
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2025-11-18 09:00:10.00000DENIED –
 PLANS INDICATE THAT THE BUILDING WOULD NOT HAVE A FIRE
 SPRINKLER SYSTEM.
 NFPA 1:13.3.2.27 WOODWORKING OPERATIONS.
 AN APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM SHALL BE
 INSTALLED IN BUILDINGS CONTAINING WOODWORKING
 OPERATIONS EXCEEDING 2500 FT2 (232 M2) THAT USE
 EQUIPMENT, MACHINERY, OR APPLIANCES; THAT GENERATE
 FINELY DIVIDED COMBUSTIBLE WASTE; OR THAT USE FINELY
 DIVIDED COMBUSTIBLE MATERIALS. [5000:29.3.5.1.2]
 NFPA 101:40.3.4 DETECTION, ALARM, AND COMMUNICATIONS
 SYSTEMS.
 40.3.4.1 GENERAL.
 A FIRE ALARM SYSTEM SHALL BE REQUIRED IN ACCORDANCE
 WITH SECTION 9.6 FOR INDUSTRIAL OCCUPANCIES, UNLESS THE
 TOTAL OCCUPANT LOAD OF THE BUILDING IS UNDER 100
 PERSONS AND UNLESS, OF THESE, FEWER THAN 25 PERSONS ARE
 ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE.
 40.3.4.2 INITIATION.
 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM SHALL BE
 BY ANY OF THE FOLLOWING MEANS:
 (1)MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1)
 (2)APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH 9.6.2.1(2) THROUGHOUT THE BUILDING,
 PLUS A MINIMUM OF ONE MANUAL FIRE ALARM BOX IN
 ACCORDANCE WITH 9.6.2.6
 (3)APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.6.2.1(3) THROUGHOUT THE BUILDING,
 PLUS A MINIMUM OF ONE MANUAL FIRE ALARM BOX IN
 ACCORDANCE WITH 9.6.2.6
 40.3.4.3 NOTIFICATION.
 40.3.4.3.1
 THE REQUIRED FIRE ALARM SYSTEM SHALL MEET ONE OF THE
 FOLLOWING CRITERIA:
 (1)IT SHALL PROVIDE OCCUPANT NOTIFICATION IN ACCORDANCE
 WITH 9.6.3.
 (2)IT SHALL SOUND AN AUDIBLE AND VISIBLE SIGNAL IN A
 CONSTANTLY ATTENDED LOCATION FOR THE PURPOSES OF
 INITIATING EMERGENCY ACTION.
 40.3.4.3.2
 POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH 9.6.3.5
 SHALL BE PERMITTED.
 HTTPS://HIGHLANDSCOFL.SHAREPOINT.COM/SITES/BCCPUBLICSAF
 ETY/SHARED DOCUMENTS/FIRE RESCUE/FIRE/PREVENTION/FMO
 DOCUMENTS 2023 AND GREATER/FMO REPORTS AND
 REVIEWS/COMMERCIAL/224 COMMERCIAL PL - BUILDING -
 25100899 11.14.25.DOCX
 PAGE 2 OF 2
 40.3.4.3.3
 EXISTING PRESIGNAL SYSTEMS IN ACCORDANCE WITH 9.6.3.4
 SHALL BE PERMITTED.
 40.3.4.3.4
 IN HIGH-HAZARD INDUSTRIAL OCCUPANCIES, AS DESCRIBED IN
 40.1.2.1.3, THE REQUIRED FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY INITIATE AN OCCUPANT EVACUATION ALARM
 SIGNAL IN ACCORDANCE WITH 9.6.3.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved