-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 25100860
Permit Number 25100860
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-11-05 09:44:44.00000FULL PAYMENT RECEIVED WITH REFERENCE NUMBER: 16885007
2025-10-30 14:16:41.00000SHEET E002: SHOW EES DISCONNECTING MEANS ADJACENT TO
 SERVICE EQUIPMENT ON EXTERIOR OF HOUSE, 706.15 (A)
 SHEET E003: SHOW SURGE PROTECTIVE DEVICE AT SERVICE,
 ALTERATION OF SERVICE EQUIPMENT, 230.67. SHOW PROPOSED
 MODEL (CURRENT OUTPUT RATING) OF ESS.
 SHEET E005: SHOW LABEL IDENTIFYING ESS DISCONNECTING
 MEANS (SEE SHEET E002 ABOVE)
 SHEET PD006: SPECIFY PROPOSED ESS MODEL (CURRENT OUTPUT
 RATING)
2025-10-27 08:42:56.00000PEBBLES@SUNSPEAR.AI