Date Text
2025-10-24 15:22:01.00000SHEET E-01: SHOW SIZE OF EXISTING FEEDER CONDUCTORS
 SUPPLIED BY EXISTING METER-MAIN; SHOW OVERCURRENT
 PROTECTION (MAIN CIRCUIT BREAKER) IN EXISTING
 DOWNSTREAM FEEDER-SUPPLIED PANEL. REFERENCE 705.12
 (B)(3)(6) AND 705.12 (B)(1)(B).
2025-10-24 14:55:20.00000REVISION, ADJUSTED LAYOUT.