Plan Review Notes For Permit 25100091
Permit Number 25100091
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2025-10-31 15:27:04.000001] ALL PLAN SHEETS WITH RIGHT HAND COLUMN "SYSTEM
 DETAILS": SHOW AC OUTPUT RATING OF PROPOSED TESLA
 POWERWALL. THE SPECIFICATION OF "13.5 KWH" IS NOT
 SPECIFIC TO THE ACTUAL INVERTER OUTPUT.
 2] SHEET PV7: SHOW A LABEL IDENTIFYING THE ENERGY
 STORAGE SHUTDOWN DEVICE. IF THE EXTERNAL SWITCH ON THE
 POWERWALL IS RELIED ON FOR THIS FUNCTION, SHOW THIS
 LABEL ON THE FACE OF THE POWERWALL INDICATING THE
 SWITCH LOCATION
 3] SHEET PV4:
 A. SHOW THE SPD AT THE GATEWAY OR AT THE INTERIOR LOAD
 CENTER, NOT A THE POWERWALL.
 B. SHOW THE ACTUAL OUTPUT RATING OF THE PROPOSED
 POWERWALL. SEE ITEM #1 ABOVE.
 C. SHOW SHUTDOWN DEVICE FOR ENERGY STORAGE SYSTEM
 (POWERWALL). PER 706.15 (A), THERE MUST BE A READILY
 ACCESSIBLE EFFECTIVELY IDENTIFIED DEVICE ON THE
 EXTERIOR OF THE HOUSE TO DISABLE ALL EXPORT POWER FROM
 THE ESS DURING AN EMERGENCY. IT IS ACCEPTABLE TO RELY
 ON THE POWERWALL'S EXTERNAL SWITCH FOR
 THIS FUNCTION IF IT IS EFFECTIVELY LABELED (SEE ITEM #2
 ABOVE)