Plan Review Notes
Plan Review Notes For Permit 25100084
Permit Number 25100084
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-10-03 13:36:50.000001] ALL PLAN SHEETS WITH RIGHT HAND COLUMN SYSTEM
 DETAILS: SHOW RATING OF TESLA POWERWALL. THE
 DESIGNATION "POWERWALL 3" IS NOT SPECIFIC TO THE
 PROPOSED MODEL RATING.
  
 2] REMOVE SPEC SHEETS FOR POWERWALL 3 EXPANSION
 UNIT/SOLAR SHUTDOWN DEVICE AS THESE COMPONENTS ARE
 SHOWN BEING INCORPORATED INTO THE INSTALLATION.
  
 3] SHEET PV7: SHOW A LABEL INDENTIFYING THE ENERGY
 STORAGE SHUTDOWN DEVICE (IN THIS INSTALLATION, THE
 FUSED SWITCH ADJACENT TO THE GATEWAY)
  
  
 4] SHEET PV4:
 A. SHOW RATING OF TESLA POWERWALL
 B. SHOW A #6 CU EQUIPMENT GROUNDING CONDUCTOR WITH THE
 CIRCUIT CONDUCTORS BETWEEN THE GATEWAY AND THE ADJACENT
 FUSED DISCONNECT.
  
  
  