Date Text
2025-10-01 15:48:32.00000NOC OR BK 3147 PG 361 IN ONBASE
2025-09-30 13:53:49.00000SHEET PV-4.0: FOR CONDUCTOR CALLOUT #3 (INVERTER TO PV
 DISCONNECT), CHANGE TO #6 CU OR CHANGE FUSES IN PV
 DISCONNECT TO 30 AMP. REFERENCE 690.9 (A).
2025-09-26 13:43:41.00000BRIANNA.SCOTCH@SUNRUN.COM