Plan Review Notes For Permit 25090602
Permit Number 25090602
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2026-02-20 08:09:11.00000SHEET PV6: ALUMINUM CONDUCTORS ARE SPECIFIED FOR
 SUPPLY-SIDE TAP. CUSTOMER REQUESTS THAT NO ALUMINUM
 CONDUCTORS BE INCORPORATED INTO THIS PROJECT, REFERRING
 TO ORIGINAL CONSTRUCTION DOCUMENTS AND CONTRACT.
 REVISED SHEET PV6 TO SHOW ALL ONLY COPPER CONDUCTORS
 USED. REMOVE ANY ALUMINUM CONDUCTORS ALREADY INSTALLED
 AND REPLACE WITH COPPER.
 SHEET PV8: NEC 690.53 REQUIRES A LABEL SHOWING MAXIMUM
 SYSTEM DC VOLTAGE CALCULATED IN ACCORDANCE WITH 690.7.
 AS OF RECENT SITE VISIT THIS LABEL IS NOT AFFIXED. PER
 PREVIOUS INSPECTION DEFICIENCY NOTES, AFFIX A MAXIMUM
 SYSTEM DC VOLTAGE LABEL TO EACH OF THREE INVERTERS,
 SHOWING THE ACTUAL CALCULATED MAXIMUM DC VOLTAGE FOR
 THE LARGEST STRING IN THAT SPECIFIC INVERTER. THE
 AFFIXED AC CURRENT/VOLTAGE LABELS CAN REMAIN.
  
 INSPECTION HOLD PLACED ON THIS PROJECT PENDING RECEIPT
 AND APPROVAL OF REVISED PLANS.