Plan Review Notes
Plan Review Notes For Permit 25090541
Permit Number 25090541
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2025-10-07 14:15:50.00000I HAVE REVIEWED THESE PLANS AND I HAVE 3 COMMENTS.
 FIRST IS I DON’T THINK THE TRAVEL DISTANCE IS
 APPROPRIATE FOR THE FIRE EXTINGUISHERS.
 I SEE ONE IN THE MIDDLE OF THE BUILDING AND THEN A
 SECOND NEAR THE BACK DOOR BUT IT APPEARS AT IF THE ONE
 IF THE MIDDLE IS TO FAR FROM THE FRONT OF THE BUSINESS.
 MAYBE I AM MISSING IT BUT I DO NOT SEE ONE NEAR THE
 FRONT “CHECK-IN” AREA BUT THERE APPEARS LIKE THERE
 SHOULD BE ONE AT THAT AREA ALSO. SECOND IS THE
 EMERGENCY LIGHT SITUATION.
 NFPA READS THAT YOU NEED A LIGHT IN ALL PATIENT EXAM
 ROOM UNLESS THAT ROOM IS ONLY OCCUPIED DURING DAY HOURS
 AND THAT ROOM HAS A WINDOW THAT WILL LET IN ENOUGH
 LIGHT.
 I HAVE NO CLUE OF THE WINDOW SITUATION SO PLEASE ADVISE
 THEM TO ADDRESS AN EMERGENCY LIGHT IS EACH PATIENT CARE
 ROOM. ALSO TO SORT OF PIGGY BACK ON THAT I DO NOT THINK
 THEY NEED ONE IN THE JANITORS CLOSET.
 THEY CAN LEAVE IT BUT I DO NOT THINK ANYONE WOULD EVER
 BE JUST STANDING IN THAT CLOSET. THIRD IS THE EXIT SIGN
 THAT IS IN THE SOT OF TOP RIGHT OF THE PLAN SHOULD BE
 ILLUMINATED FROM 2 DIRECTIONS SO BOTH SIDES OF THE HALL
 CAN SEE THE EXIT LIGHT.
 IT APPEARS ON THE PLAN TO JUST BE VISIBLE FORM ONE
 SIDE. SO AT THIS TIME I WOULD SAY THESE ARE APPROVED
 PLANS SINCE THESE 3 ITEMS CAN BE ADDRESSED LATER IN THE
 PROCESS BUT THEY NEED TO BE AWARE.
 I HAVE NO CONCERN WITH ANYTHING ELSE ON THIS PROJECT.
 THANK YOU
 RESPECTFULLY,
 CHIEF ANDREW MARCY
 AVON PARK FIRE DEPARTMENT