Date Text
2025-08-28 14:42:06.00000RECEIVED PLANS IDENTICAL TO INITIAL SUBMISSION. NO DC
 VOLTAGE LABEL IS SHOWN ON SHEET E2. THIS LABEL IS
 REQUIRED BY 690.53, AND IS IN ADDITION TO THE AC LABEL
 REQUIRED BY 690.54.