Plan Review Notes For Permit 25080358
Permit Number 25080358
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-08-12 15:08:42.00000SHEET PV2: PER FBC-R 324.6.2, AN ARRAY OCCUPYING MORE
 THAN 33% OF THE PLAN VIEW TOTAL ROOF AREA WILL REQUIRE
 A MINIMUM 36" CLEAR SETBACK ON BOTH SIDES OF A
 HORIZONTAL RIDGE.
 SHEET PV6: PER 690.53, SHOW A LABEL INDICATING MAXIMUM
 SYSTEM DC VOLTAGE FOR THE PROPOSED INSTALLATION.