2025-08-11 09:12:13.00000RESUBMIT SHEET PV3 ONLY: CHANGE AC CURRENT/VOLTAGE
 LABEL TO SHOW 23.96A.
 THIS LABEL SHOULD INDICATE THE MAXIMUM SYSTEM RATED AC
 CURRENT OUTPUT WITHOUT BEING MODIFIED BY THE 25% DEMAND
 FACTOR, SEE 690.54.