2025-07-02 12:59:03.00000SHEET PV3:
 1] PLANS INDICATE PROPOSED METER-MAIN WITH A
 SUPPLY-SIDE TAP; SHOW INTENDED METHOD OF CONNECTION FOR
 THIS TAP. IF USING LOAD-SIDE (FEEDER) TAP, SHOW
 COMPLIANCE WITH 705.12 (B)(1)(B) FOR EXISTING
 FEEDER-SUPPLIED LOAD CENTER AND SHOW COMPLIANCE WITH
 THE LABELING REQUIREMENTS OF 705.12 (B)(3)(3) FOR THE
 PROPOSED METER-MAIN.
 2] SHOW THE INSTALLATION OF AN SPD AT THE NEW SERVICE
 EQUIPMENT PER 230.67.