2025-06-24 16:20:19.00000PER CONTRACTOR EMAIL REPLY TO RFI, THE PV ARRAY IS NOT
 EXISTING, BUT IS PROPOSED TO BE INSTALLED UNDER THIS
 PERMIT. REVISE PLANS TO SHOW THIS INFORMATION. CURRENT
 PLANS INDICATE ONLY THE ADDITION OF ENERGY STORAGE TO
 AN EXISTING PV SYSTEM.
2025-06-17 09:31:54.00000PERMIT APPLICATION WRITE-IN INFORMATION INDICATES
 ENTIRE SYSTEM INSTALLATION; SCOPE OF WORK INDICATED BY
 PLANS IS ADDING ENERGY STORAGE TO EXISTING ARRAY.
 PLEASE CLARIFY IF PV SYSTEM IS EXISTING.