-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 25050858
Permit Number 25050858
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-06-05 13:57:53.00000SHEET E-1: CONDUIT/CONDUCTOR CALLOUT #4 (CONDUCTORS
 FROM GENERATOR TO ATS ON THE DIAGRAM CIRCUIT SCHEDULE)
 SHOWS #12 AWG CONDUCTORS AND A FUNCTION DESIGNATION OF
 GFCI CIRCUIT. SHOW AS (3) #6 AWG WITH #10 EGC PER THE
 DIAGRAM ON SHEET E-2 AND IDENTIFY FUNCTION AS GENERATOR
 FEEDERS.
 SHOW GENERATOR START/CONTROL CONDUIT AND CONDUCTORS ON
 THIS SHEET.
  
  
 SHEET E-2: SHOW GENERATOR START/CONTROL CONDUIT AND
 CONDUCTORS
  
  
  
  
  
  
  
  
2025-05-28 16:37:05.00000MJEAN-BAPTISTE@SBASITE.COM
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved