Plan Review Notes
Plan Review Notes For Permit 25050737
Permit Number 25050737
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-06-12 15:44:50.00000CONDITIONAL APPROVAL SUBJECT TO THE FOLLOWING ITEMS TO
 BE VERIFIED AT INSPECTION:
 1] INSTALL SURGE PROTECTIVE DEVICE AT SERVICE PER
 230.67 (ALTERATION OF SERVICE EQUIPMENT)
 2] PROVIDE, ON THE EXTERIOR OF THE STRUCTURE, READILY
 ACCESSIBLE AND IDENTIFIABLE MEANS OF DISCONNECTING ALL
 ALTERNATE SOURCES OF POWER BY ONE OF THE FOLLOWING
 MEANS:
 A. SIGNAGE ON THE FRONT OF THE GATEWAY DOOR DIRECTING
 USERS TO EMERGENCY SHUTDOWN PROCEDURE
 B. INSTALLATION OF AN E-STOP SWITCH ADJACENT TO THE
 GATEWAY, INCLUDING THE NECESSARY SIGNAGE
 C. A RATED DISCONNECTING DEVICE WITH AN EXTERNALLY
 OPERABLE HANDLE SCHEMATICALLY POSITIONED BETWEEN THE
 GATEWAY AND THE POWERWALL.