Plan Review Notes For Permit 25050230
Permit Number 25050230
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2025-06-24 08:33:07.00000HARD COPIES STAMPED
2025-06-23 09:00:26.00000PLAN REVIEW #: 25050230
 PROJECT: STEEL BLUE FABRICATION
 LOCATION: 780 CR 17 A
 OCCUPANCY: INDUSTRIAL
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 6/3/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED – BUILDING, FIRE ALARM AND SPRINKLER PLANS –
 THEY NEED PERMIT NUMBERS
 – ONLY ONE PERMIT NUMBER (PLANS HAS BUILDING,
 SPRINKLER, AND FIRE ALARM INCLUDED)
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450 BUILDING
 PLANS
 $141 + INSPECTION FEE $50 = $191 SPRINKLER PLANS
 $107 + INSPECTION FEE $50 = $157 FIRE ALARM PLANS
 BUILDING PLANS – COMMENTS LABEL BREAKERS THAT EXIT
 SIGNS AND EMERGENCY LIGHTS ARE
 SPRINKLER PLANS – PLANS ARE GOOD
 FIRE ALARM – PLANS ARE GOOD
2025-06-05 12:20:08.00000ADDITIONAL PLANS WERE EMAILED 6-4 BY
 LUPE@COOLANDCOBB.COM
2025-06-03 12:30:01.00000JASON APPROVED FIRE ALARM AND SPRINKLER BUT THEY NEED
 THE APPLICATIONS. APPLIED UNDER BUILDING PERMIT.
2025-06-03 08:32:27.00000PUT FOLDER ON G DRIVE BECAUSE OTHER PLANS MUST HAVE
 BEEN HARD COPY
  
2025-06-03 08:26:53.00000LUPE@COOLANDCOBB.COM MAILED THE REVISION DIRECTLY TO