2025-05-19 15:23:57.00000PLAN REVIEW #: 25050230
 PROJECT: STEEL BLUE FABRICATION
 LOCATION: 780 CR 17 A
 OCCUPANCY: INDUSTRIAL
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/19/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED – ONLY ONE PERMIT NUMBER (PLANS HAS BUILDING,
 SPRINKLER, AND FIRE ALARM INCLUDED)
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450 BUILDING
 PLANS
 $141 + INSPECTION FEE $50 = $191 SPRINKLER PLANS
 $107 + INSPECTION FEE $50 = $157 FIRE ALARM PLANS
 BUILDING PLANS – LSC PAGE – FIRE EXTINGUISHERS ONLY
 SHOW 4 ON THE DRAWING BUT REQUIRES 6. TRAVEL DISTANCE
 TO FIRE EXTINGUISHERS IS OVER 50 FEET APART AS
 REQUIRED. EMERGENCY LIGHTS MISSING OUTSIDE DOORS AS
 REQUIRED. THE MISSING LIGHTS ARE SHOWN ON THE
 ELECTRICAL PAGES CORRECTLY. SHALL PLACE ON LSC PAGE.
 ELECTRICAL PAGES DO NOT SHOW THE EMERGENCY LIGHTS IN
 BATHROOMS AND STORAGE; HOWEVER, THEY ARE ON THE LSC
 PAGE. UPDATE THE ELECTRICAL PAGES TO SHOW THE EMERGENCY
 LIGHTS IN BATHROOMS AND STORAGE. SIDE EXIT DOOR IN
 SHOWING INSIDE OF WELDING BAY. IF ANY WALLS OF ANY TYPE
 ARE MADE TO DIVIDE THE WELDING BAYS THE SIDE EXIT DOOR
 WILL NEED TO BE OUTSIDE OF THE WELDING BAY. MECHANICAL
 PLANS IN THE NOTE SECTION HAS NFPA 101 AS 2020, SHALL
 BE 2023.
 SPRINKLER PLANS SHOW 79 UPRIGHT HEADS, BUT THE PLANS
 ONLY HAVE 76 UPRIGHT HEADS. CORRECT THE DRAWINGS FOR
 THE 79 UPRIGHT HEADS.
 FIRE ALARM – PLANS ARE GOOD