Plan Review Notes
Plan Review Notes For Permit 25050166
Permit Number 25050166
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2025-06-18 09:11:28.000001] SHEET E3: THE LABEL REQUESTED PER ITEM #4 ON
 PREVIOUS REVIEW HAS NOT BEEN CORRECTLY WORDED. THE
 ONE-LINE DIAGRAM INDICATES THAT THE GATEWAY IS THE
 SERVICE DISCONNECT, THEREFORE, THE LABEL MUST BE WORDED
 "EMERGENCY DISCONNECT/SERVICE DISCONNECT" PER 230.85
 AND MUST BE AFFIXED TO THE EXTERIOR COVER OF THE
 GATEWAY.
  
 2] SHEET E3: THE DC VOLTAGE LABEL REQUESTED PER ITEM #6
 ON PREVIOUS REVIEW HAS NOT BEEN CORRECTLY COMPLETED.
 SHOW MAXIMUM DC VOLTAGE ON THIS LABEL PER 690.53 AND
 AFFIX TO EXTERIOR OF POWERWALL INVERTER. IT IS NOT
 REQUIRED TO SHOW DC CURRENT. THE COMBINED SYSTEM AC
 CURRENT IS 77 AMPS; THIS VALUE IS CORRECT FOR AC OUTPUT
 ONLY AND SHOULD BE INDICATED ON THE AC CURRENT/VOLTAGE
 LABEL REQUIRED BY 690.54, AFFIXED TO THE PV DISCONNECT.
2025-06-17 10:13:47.00000EMAILED IN FROM SOFIA.DEANGELIS@VOLTHOME.COM