Plan Review Notes
Plan Review Notes For Permit 25050166
Permit Number 25050166
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2025-06-06 15:17:45.000001] SHEET G1: ON SUMMARY CHART, SHOW INVERTER MODEL
 NUMBER INCLUDING RATING OF 11.5 KW
 2] SHEET E1: ON SUMMARY CHART, SHOW INVERTER RATING OF
 11.5 KW
 3] SHEET E1: SHOW INSTALLATION OF SPD AT SERVICE,
 230.67 (ALTERATION OF SERVICE EQUIPMENT).
 4] SHEET E1: SHOW EMERGENCY DISCONNECT/SERVICE
 DISCONNECT LABEL ON OUTSIDE COVER OF GATEWAY, 230.85.
 ALTERNATIVELY, THIS LABEL MAY BE SHOWN ON SHEET E3.
 5] SHEET E1: REMOVE NEUTRAL/GROUND BOND IN THE 100A PV
 DISCONNECT, 250.24 (A)(5). THIS DEVICE IS ON THE LOAD
 SIDE OF THE SERVICE DISCONNECT.
 6] SHEET E3: SHOW THE CALCULATED MAXIMUM SYSTEM DC
 VOLTAGE ON A LABEL TO BE AFFIXED TO THE INVERTER,
 690.53. DO NOT SHOW DC CURRENT AS "77 AMPS".
2025-05-16 12:17:42.00000REVISION UPLOADED ON FTP SITE. EMAIL CONTACT
 SOFIA.DEANGELIS@VOLTHOME.COM AND ALSO STORED ON G DRIVE
 IN THE EMAIL APP &PLANS FOLDER