2025-04-25 16:08:44.00000SHEET PV-4: SHOW EXACT PHYSICAL POSITION OF THE TWO
 BACKFED PV BREAKERS IN THE EXISTING LOAD CENTER.
 IMPROPER PLACEMENT WILL PRESENT A VIOLATION OF 705.12
 (B).