Plan Review Notes For Permit 25040848
Permit Number 25040848
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2025-05-06 15:34:35.00000PLAN REVIEW #: 25040848
 PROJECT: AMAZON – FIRE ALARM
 LOCATION: 1249 US 27
 OCCUPANCY: STORAGE
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/6/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED – WITH NOTES
 REVIEW FEE – $156.50 + INSPECTION FEE $50 = $206.50
 ADD MANUAL PULL STATION SHOWN ON PLANS.
 ADD HEAT DETECTOR TO THE FIRE PUMP/RISER ROOM.
 ADD TWO MORE WATER FLOW ALARMS FOR EACH RISER FOR A
 TOTAL OF 3.
 ADD DOCUMENT BOX AT FIRE ALARM PANEL
 INSPECTION OF THE ENTIRE SYSTEM ONCE COMPLETED.