2025-04-25 08:58:38.00000APPROVED – WITH COMMENTS
  KITCHEN HOOD WAS INSTALLED PRIOR TO SUBMITTING
 PLANS AND RECEIVING PERMIT NUMBER.
  DUCT WORK WELDS DID NOT HAVE LIGHT TEST
 INSPECTION ON THE GROUND PRIOR TO INSTALLATION.
  INSTALLER HAS TWO OPTIONS FOR THE WELD
 INSPECTION – ONE IS TO REMOVE DUCT WORK FOR PROPER
 INSPECTION ON THE GROUND OR LETTER FROM INSTALLATION
 COMPANY EXCEPTING RESPONSIBILITY FOR
 THE WORK. THE LETTER SHALL RELEASE HIGHLANDS COUNTY
 FIRE RESCUE MARSHAL’S OFFICE FROM
 ALL LIABILITY. THE LETTER SHALL ALSO BE SIGNED BY THE
 INSTALLER AND NOTARIZED.
  THE COMPLETE SYSTEM WILL NEED TO BE TESTED
 ONCE THE SUPPRESSION SYSTEM IS INSTALLED.
 NO PLANS HAVE BEEN REVIEWED FOR THE SUPPRESSION SYSTEM
 AND NO PERMIT HAS BEEN
 ISSUED FOR SUPPRESSION SYSTEM.
 REVIEW FEE – $200 + INSPECTION FEE $100 = $300
 ...