Plan Review Notes For Permit 25040641
Permit Number 25040641
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2025-07-16 15:26:22.00000SHEETS PV2, PV2A, & PV4: PROVIDE EXTERNALLY-OPERABLE DC
 EQUIPMENT DISCONNECTING MEANS FOR ALL STRINGS AT REMOTE
 GARAGE OR RELOCATE INVERTER TO EXTERIOR WALL OF REMOTE
 GARAGE. DC DISCONNECTING MEANS MUST HAVE RATINGS
 SUFFICIENT FOR MAXIMUM CIRCUIT CURRENT, FOR THE VOLTAGE
 AVAILABLE AT ITS LINE TERMINALS, AND FOR THE AVAILABLE
 FAULT CURRENT. REFER TO 690.15 (C).