Date Text
2025-05-12 14:42:00.00000NEEDS: SEPTIC PERMIT
2025-05-06 20:56:45.00000SHEET #8. RISER DIAGRAM NEEDS EXTERIOR DISCONNECT.
 SERVICE CONDUCTORS AND FEEDER CONDUCTORS MUST BE 4/0
 CU. EGC MUST BE #4 CU.