2025-04-17 14:03:09.00000SHEET PV-4: EGC BETWEEN NEW COMBINER LOAD CENTER AND PV
 DISCONNECT MUST COMPLY WITH TABLE 250.122 FOR
 OVERCURRENT PROTECTION PROVIDED.