Plan Review Notes For Permit 25030875
Permit Number 25030875
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2025-06-05 14:45:04.00000PLANS HAVE BEEN REVISED TO REFLECT AS-BUILT
 INTERCONNECTION (LOAD SIDE TAP TO FEEDER IN
 FEED-THROUGH SERVICE PANEL). TO ESTABLISH COMPLIANCE
 WITH 705.12 (B)(3)(3), SHOW ALL CIRCUIT BREAKERS (IF
 ANY) PRESENT IN THE FEED-THROUGH SERVICE PANEL.
 SPECIFICALLY INDICATE ON SHEET PV-4 THE INSTALLATION OF
 THE LABEL REQUIRED BY 705.12 (B)(3)(3) ON THE
 FEED-THROUGH SERVICE PANEL.