2025-03-27 13:34:56.00000SHEET PV-4: SHOW CONDUCTORS BETWEEN PV DISCONNECT AND
 SUPPLY SIDE TAP AS (3) #6 CU THWN. NOTE THAT AN
 EQUIPMENT GROUNDING CONDUCTOR IS NOT INSTALLED IN THIS
 CONDUIT BECAUSE THE SYSTEM IS BONDED TO GROUND IN THE
 PV DISCONNECT VIA THE NEUTRAL. REFERENCE 250.25 (A),
 705.11 (B), & TBL. 310.16.