2025-03-25 12:49:45.00000SHEET PV-4:
 1] ON ONE-LINE DIAGRAM, SHOW CONDUCTOR SIZE BETWEEN NEW
 60A KNIFE-BLADE DISCONNECT AND BUI.
 2] AT THE MSP, 125% OF INVERTER OUTPUT PLUS THE MAIN
 BREAKER RATING EXCEEDS 120% OF THE BUS RATING.
 NOTE ALSO THAT THE PROVISIONS OF 705.12 (B)(3)(3)
 CANNOT BE APPLIED DUE TO THE SUM OF THE BRANCH
 BREAKER RATINGS (AS SHOWN IN THE PANEL SCHEDULE ON
 SHEET PV-5A).
  
  