2025-04-17 09:26:27.00000SHEET 3 (ONE-LINE):
 1] FOR CONDUCTOR CALLOUT 3, CHANGE EGC TO #8CU
 (ASSUMING TERMINATED TO 70A BRKR IN GATEWAY), 250.122.
 2] SHOW INSTALLATION OF SPD AT GATEWAY OR AT EXISTING
 INTERIOR LOAD CENTER, 230.67.
  
 LABEL SHEET:
 1] BASED ON DATA FROM SHEET 3, THE EXISTING SYSTEM
 CONSISTS OF THIRTY-FIVE IQ7+ MICROINVERTERS. IF THIS
 DATA IS ACCURATE, THE EXISTING SYSTEM AC CURRENT OUTPUT
 IS 42.35A (35 X 1.21). THE SUM OF THIS OUTPUT PLUS THE
 TWO PROPOSED POWERWALL 3 (48A EACH) IS 138A. THIS SUM
 VALUE SHOULD BE INDICATED ON THE AC CURRENT LABEL.
 CORRECT AS NECESSARY OR SHOW JUSTIFICATION FOR 152A
 CURRENTLY SHOWN ON THIS LABEL.
 2] SHOW ESS LABEL COMPLYING WITH 706.15 (C) TO BE
 AFFIXED TO EACH POWERWALL 3. THIS LABEL MUST IDENTIFY
 THE ESS DISCONNECTING MEANS AND SHOW NOMINAL AC VOLTAGE
 PLUS MAXIMUM DC VOLTAGE.
2025-04-16 15:02:19.00000REVISION STUBILLAS@TESLA.COM