Plan Review Notes
Plan Review Notes For Permit 25030469
Permit Number 25030469
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-03-18 08:46:08.00000REJECTED NOTES SENT TO CONTRACTOR 3/18
2025-03-14 16:47:18.000001] PROVIDE SPECIFICATION SHEETS ON PROPOSED TESLA
 POWERWALLS.
 2] SHOW LABEL ON NEW GATEWAY INDICATING TOTAL SYSTEM
 CURRENT OUTPUT (EXISTING PV SYSTEM PLUS POWERWALL
 BATTERY OUTPUTS).
 3] SHOW CONDUCTOR SIZE BETWEEN EXISTING PV DISCONNECT
 AND GATEWAY.
 4] SHOW LABEL INDICATING EXACT LOCATION AND MEANS OF
 DISCONNECTING ENERGY STORAGE SYSTEM. THIS DISCONNECTING
 MEANS MUST BE ON THE EXTERIOR OF THE HOUSE, READILY
 ACCESSIBLE, AND PERMANENTLY IDENTIFIED.
2025-03-14 15:53:29.00000STUBILLA@TESLA.COM