-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 25030445
Permit Number 25030445
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-03-14 14:10:42.00000SHEET PV-3: CHANGE PV DISCONNECT FUSES TO 40 AMP (18 X
 1.58 X 1.25 = 35.55). IT IS NOT REQUIRED TO RE-SUBMIT
 THE ENTIRE PLANSET, ONLY THE AFFECTED SHEET.
2025-03-14 08:30:29.00000ELENA.SOLORZANO@MOMENTUMSOLAR.COM