Plan Review Notes For Permit 25020843
Permit Number 25020843
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2025-03-04 16:17:55.00000EMAILED 4:17 PM 3/4/2025 CAS
2025-02-27 12:41:03.00000SHEET PV4: CLARIFY INTERCONNECTION METHOD IN MSP. A
 "LUG KIT" IS SPECIFIED AS A TERMINATION ON THE EXISTING
 100A SUBPANEL FEEDERS; THE SPECIFIED CONNECTION METHOD
 IS UNCLEAR.
 IF USING A FEEDER TAP, SHOW FEEDER CONDUCTOR SIZE AND
 OVERCURRENT PROTECTION ON THE LOAD END OF THE FEEDER
 (I.E., A MAIN BREAKER IN THE EXISTING SUBPANEL). FEEDER
 TAPS MUST COMPLY WITH 705.12 (B).
 IF USING A BUS CONNECTION, SHOW SERVICE DISCONNECT IN
 MSP.